CRF In Row Cooling Unit (Refrigerant pump)

In case you do not find the type or model in the website We can customized according to your request.
Contact Now
  • Features
  • Technical Data
  • Application
  • Certification
  • Part List
  • Reference
CRF Row-Based Air Conditioner (refrigerant pump) can use atmospheric natural cold source for cooling computer room.lt installed close to the heat source, shorten the flow path of cold air, and accurately process the sensible heat generated by the server. It is an ideal choice for green and energy-saving data centers and all kinds of electronic equipment rooms.

CRF Row-Based Air Conditioner (Refrigerant pump)

Indoor unit model

CRF3025

CRF3040

CRF3060

Main power supply

380V3Ph~50Hz

Air supply

Front air supply

Performance  parameter

Cooling  capacity(kW)

25

40

60

Sensible capacity (kW)

25

40

60

Max. operation current FLA (A)

37

48.2

57.2

Compressor   QTY

1

Fan  type

EC centrifugal fan

Fan  QTY

6

2

3

Circulating air volume(m³/h)

5000

8000

12000

Heating  capacity(kW)

3

6

9

Humidification(kg/h)

1.5

3

4.5

Connecting pipe size(30m)

Liquid   pipe(mm)

16

Gas    pipe(mm)

22

Humidification inlet pipe (Internal thread)

G3/4"

Water  pump  drain  pipe(mm)

ID12*0D16

Natural drain pipe(mm)

ID16*OD24

Unit dimension and weight

Dimension-W(mm)

300

600

600

Dimension-D(mm)

1200

Dimension-H(mm)

2000

Weight(kg)

210

250

310

Outdoor unit performance parameter(40℃)

Flat-plate outdoor unit model

CMTO38SP

CMT055SP

CMTO88SP

Outdoor unit performance parameter(45℃)

Centralized outdoor unit model

CMTO44FP

CMTO66FP

CMT099FP

Electronic element specification

Air  switch  recommended(A)

40

63

63

Indoor  power  cable  diameter(mm²)

4*6.0+1*6.0

4*16+1*16

4*16+1*16

Outdoor  power  cable  diameter(mm²)

4*1.5+1*1.5

Note:
1. Standard working conditions: indoor return air temperature 37°C, RH 24%, air cooled outdoor ambient temperature 35℃, ESP=10Pa;
2. Only cooling + electric heating or constant temperature and humidity type can be selected. The maximum working current and the recommended air switch are configured according to the constant temperature and humidity unit.
3. The above table is only part of the parameters, and the specific configuration is subject to the name plate. If you want to choose a pump cabinet or know more details, please contact us.

Application: Small and medium-sized data centers, modular data centers, cabinet cold (hot) aisle transformation, medium and high thermal density communication equipment and computer rooms. etc

Country: Indonesia
Application:data center
Cooling capacity: 36.7kW
EER: 3.96
Air volume: 12750m3/h
Refrigerant: R410A
Power supply: 380V/3P/50Hz

Country: Philippines
Application: MRI room in hospital
Cooling capacity: 29.8kW
Electric heating: 11kW
Air volume: 7500m3/h
Refrigerant: R407C
Power supply: 400V/3P/60Hz
Downflow air supply

Country: USA
Application: Data center cooling
Cooling capacity: 18kW
Air volume: 4100m3/h
Refrigerant: R410A
Power supply: 400V/3P/60Hz
Remote control

Country: Tajikistan
Application: data base station
Cooling capacity: 13.1kW
Air volume: 2400m3/h
Refrigerant: R407C
Power supply: 380V/3P/50Hz

Country:China
Application: wind farm
Cooling capacity: 50kW
Air volume: 12000m3/h
Refrigerant: R22
Power supply: 380V/3P/50Hz

 

 