1. Compressor: Vortex type compressor, adopt international brand fully enclosed vortex type maintenance free compressor
2. Heat exchanger: 5HP or bigger model, use high efficiency shell and tube evaporator and condenser
6. In order to adapt to the different requirements of all walks of life, the use of different series of scroll compressor, refrigeration water temperature from 15 degrees to -35 degrees, sophisticated technology to ensure the stability of the work under the extreme conditions
|
Type |
SLPA- |
||||||||||||
|
3.1 |
5.1 |
8.1 |
10.1 |
12.1 |
15.1 |
20.1 |
20.2 |
25.2 |
30.2 |
40.2 |
|||
|
Refrigerant capacity |
KW |
8.8 |
14.4 |
25.5 |
29.0 |
32.7 |
41.1 |
55.3 |
58.0 |
65.4 |
82.2 |
110.6 |
|
|
×103 kcal/h |
7.6 |
12.4 |
21.9 |
25.0 |
28.1 |
35.4 |
47.6 |
49.9 |
56.3 |
70.7 |
95.2 |
||
|
TR |
2.5 |
4.1 |
7.2 |
8.3 |
9.3 |
11.7 |
15.7 |
16.5 |
18.6 |
23.4 |
31.5 |
||
|
Holistic power |
KW |
3.1 |
5.2 |
8.1 |
9.5 |
10.9 |
14.4 |
19.3 |
18.4 |
20.5 |
28.6 |
38.0 |
|
|
Holistic current |
A |
5.7 |
9.6 |
14.8 |
17.3 |
19.9 |
26.3 |
35.3 |
33.6 |
37.6 |
52.3 |
69.5 |
|
|
Compressor |
Input power |
kW |
2.6 |
4.3 |
7.0 |
7.9 |
8.9 |
12.4 |
16.6 |
15.7 |
17.9 |
24.9 |
33.3 |
|
Operating current |
A |
4.6 |
7.6 |
12.4 |
14.0 |
15.9 |
22.1 |
29.6 |
28.0 |
31.8 |
44.3 |
59.2 |
|
|
Qty. |
set |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
|
|
Condensation axial fan |
Input power |
KW |
0.19 |
0.42 |
0.38 |
0.84 |
0.84 |
0.84 |
1.14 |
1.14 |
1.14 |
1.50 |
2.52 |
|
Input current |
A |
0.50 |
0.85 |
1.00 |
1.70 |
1.70 |
1.70 |
3.00 |
3.00 |
3.00 |
3.84 |
5.10 |
|
|
Evaporator |
flow |
L/min |
25 |
41 |
73 |
83 |
93 |
118 |
158 |
166 |
187 |
235 |
316 |
|
Interface |
mm |
25 |
25 |
32 |
32 |
32 |
40 |
40 |
40 |
50 |
50 |
65 |
|
|
Chilled water pump |
Input power |
KW |
0.37 |
0.55 |
0.75 |
0.75 |
1.10 |
1.10 |
1.50 |
1.50 |
1.50 |
2.20 |
2.20 |
|
Head |
mH2O |
16 |
21 |
22 |
19 |
17 |
25 |
24 |
24 |
23 |
22 |
21 |
|
|
Tank nominal capacity |
L |
70 |
75 |
100 |
115 |
145 |
250 |
270 |
270 |
320 |
360 |
400 |
|
|
Overall dimensions |
Length |
mm |
950 |
950 |
1200 |
1350 |
1400 |
1600 |
1950 |
1950 |
2100 |
2200 |
2450 |
|
width |
mm |
700 |
700 |
850 |
850 |
850 |
1000 |
1250 |
1250 |
1250 |
1250 |
1350 |
|
|
|
Height |
mm |
1050 |
1050 |
1550 |
1550 |
1550 |
1600 |
1600 |
1600 |
1600 |
1850 |
2050 |
|
Total weight |
kg |
150 |
200 |
285 |
350 |
450 |
600 |
830 |
830 |
1050 |
1250 |
1350 |
|
- 22 Jan,2018429kW dry cooler for Singapore wastewater treatment factory.
- 22 Jan,2018176Kw water cooled chillers finished for Malaysia factory
- 22 Nov,201752kw dry cooler finished for local client.
- 22 Nov,2017AHU cooling coils and centrifugal fan for Saudi Arabia client
- 22 Nov,2017Waiting loading container for South Africa client, air cooler
- 22 Nov,2017Fin type condenser finished for French client
- 22 Nov,20171580KW water cooled screw chiller finished.